Neutralizer |
| DAVIES "BOILER-NEUTRO" is a special liquid blend of alkaline materials and is used immediately after acidizing a boiler. "BOILER-NEUTRO" also will attack certain types of scale that acid has difficulty attacking, such as silica acale, which is most difficult to attack. "BOILER-NEUTRO" has been found to be effective in knocking loose some last traces of scale that may be left in boiler and neutralize boiler at the same time. |
|
|
|
| 1. | Drain all water treated with acid. |
| 2. | Remove all loose excess scale in boiler. |
| 3. | Fill boiler with fresh water. |
| 4. | Add enough "BOILER-NEUTRO" to bring the pH of boiler to 12 or 13. (Approximately 1 gallon "BOILER-NEUTRO" to 100 gallons water will generally bring the pH to 13. Slightly more may be needed depending on conditions.) |
| 5. | Bring water temperature up to approximately 180 degrees and circulate for approximately one hour. |
| 6. | Drain boiler completely. |
| 7. | Remove all remaining loose excess scale in boiler. |
| 8. | Disconnect circulating pump, close up boiler, fill with fresh water. |
| 9. | Add enough "NO-SCALE" boiler compound to bring pH to 13 and boiler is ready for operation. |
|
The above procedure is for badly scaled boilers. If boiler is not badly scaled, the amount of "BOILER-NEUTRO" needed will be much less and it will not be necessary to circulate for 1 hour. For light scale, simply add enough "BOILER-NEUTRO" to bring pH of water to a pH of 9. Circulate for 15 minutes. Distriutor inquiries are welcome. |